1415015-1
SR6A4024 - V23050-A1024-A533
The SR6A4024 - V23050-A1024-A533 is a high-performance power relay designed for reliable switching in HVAC systems and other industrial applications. With a compact Printed Circuit Board mount type, this relay features six poles with 3 Form A (NO) and 1 Form B (NC) contact arrangement, offering versatile control options. Rated for a maximum switching voltage of 400 VAC and a contact voltage of 250 VAC, it ensures robust operation in demanding environments. The coil operates at 24 VDC with a low current draw of .05 A, boasting energy efficiency. With RoHS compliance and a contact material of Silver Tin Oxide (AgSnO2), this relay guarantees both environmental sustainability and long-lasting performance. Available for immediate shipping, it is a crucial component for system reliability.
Product Category: | |
Manufacturer: | TE Connectivity |
Manufacturer Part Number: | TE Connectivity 1415015-1 |
Amperage: | 8 A |
Mount Type: | Printed Circuit Board |
Contact Material: | Silver Tin Oxide (AgSnO2) |
Number of Poles: | 6 |
Coil Resistance: | 480 Ω |
Coil Current: | .05 A |
Coil Voltage: | 24 VDC |
Maximum Switching Voltage: | 400 VAC |
Contact Voltage: | 250 VAC |
Contact Arrangement: | 3 Form A (NO) + 1 Form B (NC) |
SKU: | AMP1415015-1 |
series: | SCHRACK SR6 A/B/C/V |
Product Weight: | 90 g / 1.058 oz |
Contact Current Class: | 5 - 10 A |
Terminal Type: | PCB-THT |
Contact Special Features: | Force Guided Contacts |
Product Height: | 16.5 mm / .65 in |
Height Class (Mechanical): | 16 - 20 mm |
Insulation Clearance Between Contact & Coil: | 5.5 mm / .217 in |
Insulation Clearance Class: | 5 - 8 mm |
Product Length: | 55 mm / 2.167 in |
Length Class (Mechanical): | 50 - 60 mm |
Product Width: | 16.51 mm / .65 in |
Width Class (Mechanical): | 16 - 20 mm |
Coil Magnetic System: | Monostable, DC |
Coil Power Rating Class: | 1000 - 1500 mW |
Coil Power Rating DC: | 1200 mW |
Contact Switching Load (Min): | 10mA @ 5V |
Contact Limiting Breaking Current: | 8 A |
Contact Limiting Continuous Current: | 8 A |
Contact Limiting Making Current: | 8 A |
Contact Limiting Short-Time Current: | 8 A |
Insulation Creepage Between Contact & Coil: | 5.5 mm / .217 in |
Insulation Creepage Class: | 3 - 5.5 mm |
Insulation Initial Dielectric Between Adjacent Contacts: | 3000 Vrms |
Insulation Initial Dielectric Between Coil & Contact Class: | 3500 - 4000 V |
Insulation Initial Dielectric Between Open Contacts: | 1500 Vrms |
Insulation Initial Dielectric Between Contacts & Coil: | 4000 Vrms |
Power Relay Type: | Force-Guided |
Environmental Ambient Temperature (Max): | 70 °C / 158 °F |
Environmental Ambient Temperature Class: | -25 - 70 °C |
Environmental Category of Protection: | RTIII |
Supplier Product: | Power Relays |
Part Alias: | V23050-A1024-A533,1415015-1 |
Environmental Initiative Details
Environmental Initiative: | RoHS |
---|---|
Compliant: | Unknown |
Date of this Information: | Unknown |
Notes: |
Product Change Notice
Effective Date | Description of Change | Download |
---|---|---|
10/14/2021 | P-21-021583 - Document clarification. We previously reported in April 2020 that these products contained SVHC BPA above the REACH threshold of 0,1%. This was based on an updated material declaration from our supplier of the terminal sealing adhesive in its liquid state, as delivered to us. We have now found out, that the majority of this SVHC vanishes during chemical reactions while the adhesive is cured. After curing, which represents the state in which all our relays are shipped, the content of SVHC BPA is below the REACH threshold of 0,1% and therefore the relays are REACH compliant without exemptions. Our Statements of Compliance for the relays have been updated accordingly and are linked to the affected products on TE.com. We assume, that this threshold was actually never surpassed on our finished product since the terminal sealing adhesive was introduced in September 2017. | Download |
04/29/2021 | P-21-020820 - Product Improvement. we decided to improve our packaging for SR4 and SR6 relays to reduce the impact of the environmental conditions during the shipment, especially the harsh conditions of humid and salty air during oversea transport. Therefore instead of placing the carton-tubes directly into the shipping box, we added a transparent plastic bag in the shipping box in which the carton-tubes are inserted, together with a small desiccant bag. No changes were made to the shipping box, the carton tubes or their orientation in the box, only the plastic bag and desiccant bag were added. In order to benefit from the improved packaging as soon as possible, all lots produced since 5th of April 2021 (calendar week 14 or date code 2114) are featuring this improved packaging design. | Download |
08/19/2020 | E-20-008880 - Manufacturing / Process Requirements.The following part numbers contain contact rivets, for which TE has approved an additional supplier (second source). The contacts from the additional supplier are identical in form and dimensions, in their material, manufacturing process as well as their specification. The product specifications of SR4 and SR6 relays remain unchanged. | Download |
04/24/2020 | P-20-018970 - SoC/REACH Correction & Clarification. , since September 2017 we use an adhesive, which contains SVHC BPA above REACH threshold of 0.1%. Our Statement of Compliance for the relays did not consider this fact, as it is based on a material declaration from our supplier, which turned out to be wrong. After detecting this error, since March 2020 we corrected the product compliance declaration accordingly and these are linked to the affected products on our homepages. We are working to find potential alternative adhesives, which might enable us to declare containing REACH SVHC below threshold again, but for the time being, the SoC similar to the enclosed is valid for the SR4M/D & SR6 relay series. | Download |
07/19/2019 | E-19-011155 - As of July 15th 2019, TE Connectivitys SR6 6 pole Force Guided Relay has regained the approval to carry the China Compulsory Certificate (CCC) mark of product certification. Starting with Datecode 1930, all eligible SR6 Relays produced thereafter will have the CCC mark printed on them. | Download |